The X-22S™ eight-analog-input expansion module is used with an X-400™ or X-600M™ controller. It has eight precision analog inputs that can be configured for various voltage ranges and 4-20mA sensors.
The X-22S™ is ideal for measuring precision analog voltages. This includes monitoring temperature, electrical current, pressure, and fluid levels. It is a great fit for environmental monitoring, wastewater, and greenhouse applications.
The X-22S™ employs a 16-bit SAR A/D converter and can make both single or differential input measurements. A 5.0V reference output can be used to power potentiometers or other resistance sensing sensors. One or more X-22S™ expansion modules can be connected with a ribbon cable that provides both power and communication.
The X-400™ is a web-enabled controller that allows for up to 32 added expansion modules and/or remote I/O devices. Expansion modules are connected directly to the X-400 via ribbon cable, or remotely with other CBW devices via P2P—allowing for monitoring and control of up to 64 I/O.
The X-400C offers wireless capability with a built-in cellular modem.
Expandable, Up to 64 I/O
Relays, Analog & Digital Inputs
Up to 16 temp sensors
Cellular version available
[frequentlyBought ids="7635,34491,7624,7577"]
View Product
This product has multiple variants. The options may be chosen on the product page
The X-600M™ is one of the most capable and flexible ControlByWeb PLCs. Add up to 64 expansion modules and remotely monitor and control up to 1,024 I/O. Create custom logic through the X-600M interface and run your application through a built-in web server and web browser.
Expandable, Up to 1,024 I/O
Relays, Analog/Digital/Thermocouple Inputs
Up to 32 Temperature Sensors
GUI Dashboard
[frequentlyBought ids="7635,7621,7318,7289"]
View Product
This product has multiple variants. The options may be chosen on the product page
(Example images are shown. Label and terminal connector may differ)
Specifications
Power Requirements
Voltage: 9-28VDC (supplied via the X-400 controller, 24V recommended)
Max Current:
Power Supply
Current (voltage mode)
Current (current mode)
9 VDC
42 mA
83 mA
12 VDC
32 mA
62 mA
24 VDC
17 mA
33 mA
Analog Inputs
Number of Inputs: 8
Type: Single-ended, differential, 4-20mA (0-20mA), or a combination
Input Range: ±1.28V, ±2.56V, ±5.12V, ±10.24V, 4-20mA **Note that inputs have high impedance so input range can easily be adjusted using external resistors. Example: 0 to 48 Volts
Resolution: 16-bit, SAR
Reference Output
Voltage: 5.00V
Accuracy: 0.04%
Temperature Coefficient: 3ppm/°C Max
Current: 25mA max*
*Maximum current from the reference may be increased if the environmental temperature is decreased. See users manual for more information.
Connectors
Inputs: 14-Position, 3.81mm terminal spacing, Removable. For 16-28 AWG wire.
Expansion Connector: Ribbon cable, 10-conductor, polarized, 2×5-position, 0.100″ pitch Provides power and communications for expansion modules (Communications: RS-485)
For your convenience we have set up a live X-600M unit connected to several expansion modules (i.e., X-11S, X-12S, X-13S, X-15S,and X-16S). The X-22S will be connected and used similarly to these expansion modules. These expansion modules contain a variety of inputs and outputs that allow you to see how the X-600M works with its expansion modules. By clicking the links below you have full access to these live units. You can make changes to the configuration and settings through the setup pages and you can control the expansion modules’ relays, and view the current status of the inputs, and monitor temperature (X-600M & X-13S) through its dashboard page.
The diagrams illustrate how this demonstration is wired. The relays on all expansion modules are not connected to a load; however, you can still access and control the relays by turning them on or off through the X-600M dashboard. The X-600M is also wired to a temperature sensor, and the X-13S is connected to a thermocouple. Both sensors can be monitored on the X-600M’s dashboard. The digital input states on the X-15S only changes when a voltage is applied to the inputs. For this demonstration, we have connected one of our X-332 controllers to Input 1 on the X-15S. You can apply a voltage to this input by accessing the control page for the X-332 (Digital Input Control Page).
Important Information
Multiple users may be accessing this device simultaneously so the device can change while you are using it.
This unit will be reset to factory defaults daily at 2:30AM MST.
Please DO NOT change network or password settings.
The X-418™ is a web-enabled analog module with eight configurable analog-to-digital inputs. Perfect for sensor monitoring for tank/bin level, pressure, flow, current, and more.
8 Analog Inputs (multi-function)
±1.28V, ±2.56V, ±5.12V, ±10.24V
4-20mA (Inputs 1-4 only)
[frequentlyBought ids="7621,34491,7916,7781"]
View Product
This product has multiple variants. The options may be chosen on the product page
The X-412™ is a powerful analog-to-digital Ethernet I/O PLC. It features 4 analog inputs, 4 relays, and a built-in web server for infinite control and monitoring possibilities.
4 Relays
4 Analog Inputs
New Cellular Option: The X-412CW model includes a cellular modem, compatible with our cellular data plans. WiFi is Now Available. The X-412CW model includes WiFi capability which allows for more flexibility and cost savings for your application.
[frequentlyBought ids="7624,7916,34491,7781"]
View Product
This product has multiple variants. The options may be chosen on the product page